Offers enhanced fault-tolerance and reliability with N+1 configuration support and hot-swappable whole UPS replacement options
Included parallel PDU with manual bypass switching enables hot-swappable replacement of either 10kVA power module at any supported load level, with no interruption to connected equipment
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal during brownouts as low 100V and overvoltages as high as 300V
20kVA on-line double-conversion UPS with C19 outlets. Ideal for critical server, network and telecommunications equipment in a 12U rack/tower configuration. System delivers complete N+1 redundancy when used at loads up to 10kVA, and non-redundant operation at loads between 10 and 20kVA. Fault-tolerant auto-bypass prevents unexpected service interruptions during UPS overload or internal fault conditions.
Offers enhanced fault-tolerance and reliability with N+1 configuration support and hot-swappable whole UPS replacement options
Included parallel PDU with manual bypass switching enables hot-swappable replacement of either 10kVA power module at any supported load level, with no interruption to connected equipment
Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions
Full-time active power conditioning provides clean, continuous dual-conversion AC output free of voltage fluctuations, power interruptions and line noise
Maintains full-time sine wave output within 2% of selectable 200/208/220/230/240V nominal during brownouts as low 100V and overvoltages as high as 300V
Supports 50/60Hz operation for worldwide frequency compatibility
Expandable runtime is supported with optional BP240V10RT3U, BP240V557C-1PH, BP240V787C-1PH, BP240V1037C-1PH and BP240V1407C-1PH external battery packs
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement
Includes free PowerAlert monitoring software packages, PowerAlert LOCAL for desktops and small business networks, PowerAlert NSA (network shutdown agent) for larger networks and PowerAlert NMS (network management system) for monitoring up to 250 SNMP-enabl
Supports detailed monitoring of equipment load levels, self-test data and utility power conditions via built-in RS-232 and USB interfaces
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Supports emergency power off (EPO) via built-in interface
Included rail kit supports 12U 19 inch rackmount installation in 4 post racks
Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks (4 required for SU20KRTG)
Optional 2-9USTAND supports upright tower placement (2 required for SU20KRTG)
Front panel LEDs and LCD readout with scroll controls and password option supports visual monitoring of all major UPS functions and advanced UPS settings for charge level, nominal voltage selection, frequency conversion and other operational parameters
LED/LCD display panel rotates for viewing in rackmount or tower configurations
Network-grade AC surge and noise suppression
Industrial mode option (factory preset) enables supports high current startup loads by momentarily switching to bypass mode in response to short duration overload conditions
Warranty - Yes
Rackmountable - Yes
UL Rated - Yes
Spec Sheet available - Yes
Operating Temperature (Maximum):
40 C
Operating Temperature (Minimum):
0 C
Estimated Runtime:
4.30 minutes
Estimated Runtime:
0.07 hours
Number of Outlets:
8
Rack Units (Height):
12
Rackmountable:
Yes
UL Rated:
Yes
Depth:
655.83 mm
Height:
130.56 mm
Width:
444.50 mm
Product Weight:
20 kg
Shipping Weight:
272.40 kg
Warranty (Length/Type):
2-year Limited
Output volt amp capacity:
20000 VA
Output Watt Capacity:
18000 W
Nominal Output Voltage (Supported):
200/208/220/230/240 V
Frequency Compatibility:
50/60 Hz (auto-selectable)
Built-in UPS output receptacles:
8 C19 outlets
Rated input current (at maximum load):
112.2A (200V), 108A (208V), 102A (220V), 97.6A (230V) and 93.6A (240V)
Nominal Input Voltage (Supported):
200/208/220/230/240 VAC
Input Connection Type:
Hardwire
Battery Full Load Runtime:
4.3 minutes (18000W)
Battery Half Load Runtime:
12.5 minutes (9000W)
DC Battery System Voltage:
240 VDC
Primary Form Factor:
Rackmount
Shipping Dimensions:
5.25 x 17.5 x 25 inches
UPS housing material:
Steel
Cooling Method:
Fan
Package Includes:
Two SU10000RT3UPM UPS power modules, two BP240V10RT3U battery packs, one SUPDMB20KIEC PDU with bypass switch, 4-post rackmount installation rails and PowerAlert software and cable